Kirloskar 250kVA Diesel Generators

Home > 250kVA Diesel Generators

Kirloskar 250kVA Diesel Generators

The KG1-250WS Model of Genset operates at a frequency of 50 Hz and a power factor of 0.8 lagging, making it suitable for a wide range of industrial and commercial applications. It runs on 415V three-phase power and is classified under the G3 governing class, ensuring stable and efficient performance. With a noise level of less than 75 dBA, the genset offers quiet operation. Fuel consumption varies depending on the load, with rates of 56.9, 42.6, and 29.9 liters per hour. It features a large 460-liter fuel tank, providing extended operational time. Weighing between 4100 and 4500 kg, the genset has overall dimensions of 4300 mm (length), 1700 mm (width), and 1970 mm (height). Additionally, it is equipped with a 24-volt DC electrical battery for reliable starting, making the KG1-250WS an ideal choice for continuous power supply in demanding environments.

Kirloskar 250 kva Generator Set

At Goel Power, we specialize in providing top-quality 250 kVA diesel generators that deliver reliable and efficient power solutions for various applications. Designed to meet the needs of industrial, commercial, and residential sectors, our 250 kVA generators ensure uninterrupted power supply, even in the most demanding conditions. Featuring a robust engine and advanced technology, these generators offer exceptional power output and fuel efficiency, making them an ideal choice for businesses and industries seeking reliable power backup.

Our Kirloskar gensets are engineered with sound-resistant and environmentally friendly canopies, ensuring quiet and eco-friendly operation. The high horsepower (HHP) range, including the SL90 and DV series, leads the market with its superior performance and fuel efficiency. These gensets are equipped with the latest technologies to meet stringent CPCB emission norms, ensuring compliance while delivering clean and efficient power for large-scale operations. With best-in-class fuel economy and excellent block-loading capabilities, Kirloskar HHP gensets provide exceptional performance that exceeds expectations.

If you’re looking for a 250 kVA generator, Goel Power offers the perfect solution. Our Kirloskar generators are known for their durability, reliability, and performance. Check out our competitive 250 kVA generator prices in India and experience the unmatched quality of Kirloskar gensets. For more details or to inquire about Kirloskar 250 kVA generator prices, contact us today. Invest in a Kirloskar generator and enjoy seamless, uninterrupted power for all your needs.

Features of Kirloskar 250 kva Generator Set

1. Prime Rating vs Standby Rating

When selecting a Genset, it is essential to understand the difference between Prime Power and Standby Power ratings. Prime Power Gensets are designed for unlimited operational hours and can handle a 10% temporary overload. In contrast, Standby Power Gensets are designed to operate for up to 200 hours annually during emergencies.

Kirloskar offers Prime Power Gensets as a standard solution to ensure continuous and reliable performance. For Standby Power requirements, users can contact Kirloskar to find the most suitable rating for their needs.

2. Engine Capacity: No Replacement for Displacement

The engine capacity (cc) plays a critical role in determining the performance and stability of a Genset. Higher engine capacity ensures robust, consistent operation and enables the Genset to respond quickly and efficiently to sudden load variations.

With a higher displacement engine, Kirloskar Gensets deliver superior performance, ensuring smooth load handling even under demanding conditions.

3. Best-in-Class Fluid Efficiency: Fuel and DEF

Kirloskar Gensets are engineered to deliver an optimal balance between CPCB compliance and fuel efficiency, resulting in significant savings on operational costs.

O2E Series (Optimal Operating Efficiency):

  • In real-world scenarios, Gensets rarely operate at full load capacity. Variations in power demand across day and night, weekdays and weekends, or seasonal changes often result in 50-70% average loading.
  • Kirloskar’s O2E Series optimizes fuel efficiency from 100% down to 50% load, ensuring substantial savings even at partial loads.
  • Enhanced DEF (Diesel Exhaust Fluid) efficiency further contributes to cost savings with an optimized DEF tank size.

With this double advantage of fuel and DEF optimization, Kirloskar Gensets delivers unmatched performance and operational economy.

4. Advanced CRDi Technology for Superior Performance

Kirloskar Gensets feature Common Rail Direct Injection (CRDi) technology, a significant upgrade over traditional mechanical fuel injection systems. CRDi systems offer:

  • Precise fuel control and multiple injections for enhanced efficiency
  • Reduced noise and emissions
  • Smooth, smoke-free performance with maximized fuel atomization

The high-pressure common rail system used in Kirloskar CPCB IV+ Gensets ensures superior fuel combustion and reliability. Additionally, ‘A’ class diesel filters provide exceptional filtration efficiency, extending the life of the engine and enhancing overall performance.

With advanced CRDi technology, Kirloskar Gensets set new benchmarks for fuel efficiency, reduced emissions, and reliable operation.

5.Genset Monitoring at Your Fingertips

Kirloskar Gensets come equipped with the Kirloskar Remote Monitoring System, offering real-time Genset performance insights and location tracking. This system can be easily accessed via mobile devices or desktop computers.

Key Features of Remote Monitoring:

  • Real-Time Alerts: The system identifies and highlights critical parameters that require immediate attention.
  • Emergency Notifications: Alerts are sent directly to the user’s mobile via text messages.
  • Service Assistance: In case of an emergency breakdown, notifications are also sent to the nearest authorized service dealer, ensuring prompt support and minimal downtime.

6. On-board diagnostics for Superior Uptime

Kirloskar Gensets are designed for unmatched reliability with advanced diagnostic capabilities. Combined with the Kirloskar Remote Monitoring System, the onboard diagnostics allow:

  • Real-Time Performance Monitoring: Continuously track emissions and service-critical parameters.
  • Early Issue Detection: Proactively diagnose and resolve issues before they lead to system failure, ensuring uninterrupted operation and extended uptime.

7. State-of-the-Art Genset Controller

Kirloskar Gensets place control at your fingertips with their microprocessor-based Genset controller. This advanced system provides detailed insights and complete control over critical Genset functions.

Monitoring Features:

  • Phase Voltages & Currents, Frequency, Genset kVA, kW, kWh, kVAr, Power Factor
  • Lube Oil Pressure, Engine Temperature, RPM, Run Hours, Number of Starts, Fuel Level
  • Auto/Manual Stop, Battery Charge Condition, AMF (Auto Mains Failure) Feature

Diagnostic Features:

  • Battery Charging Failure, Over/Under Speed, Over Current, Over/Under Voltage, Over kW
  • Phase Sequence, Phase Missing, Mains Under Voltage, Low Fuel Level
  • Low Lube Oil Pressure, High Engine Temperature, Low/High Battery Voltage
  • Over Crank Protection, Routine Maintenance Indicator, Genset Test Facility, Mains Frequency Monitoring

Optional Features:

  • Modbus Communication for seamless data integration and advanced control.

With these comprehensive monitoring, diagnostic, and optional features, Kirloskar Gensets ensures peak performance, maximum uptime, and operational efficiency.

8.Peace-of-Mind Ownership with Kirloskar Gensets

Kirloskar Gensets are renowned for their robust design, unmatched reliability, and long operational life. Built on well-established and proven engine platforms, Kirloskar ensures compliance with the latest CPCB norms while enhancing durability and on-site serviceability.

Key Benefits:

  • Proven Technology: Carefully selected technologies enhance the durability and reliability of Gensets.
  • Trouble-Free Performance: Engineered for years of consistent, hassle-free operation.
  • Low Cost of Ownership: Minimized maintenance and operational costs ensure a cost-effective solution.
  • Prompt Service Support: Backed by Kirloskar’s reliable support network for quick and efficient service.

With Kirloskar Gensets, you enjoy peace of mind through dependable performance, low operational costs, and superior product reliability.

9. Advanced Alternator Features

Kirloskar Alternators are designed for compactness, rugged performance, and best-in-class efficiency. Featuring advanced Digital AVR (Automatic Voltage Regulator) technology, Kirloskar Alternators ensure:

  • Improved Voltage Regulation: Precise voltage control for stable power output.
  • Faster Response Time: Quick adaptation to load changes, ensuring smooth operations.

These features make Kirloskar Alternators the ideal choice for efficient and reliable power generation.

10. Compact Footprint for Space Efficiency

Kirloskar CPCB-compliant Gensets are designed with a compact footprint, ensuring significant space savings without compromising performance. Despite advanced upgrades to meet CPCB norms, Kirloskar maintains the Genset’s compact and efficient design, making it perfect for space-constrained installations.

Key Highlights:

  • Space-Saving Design: Compact footprint for optimized use of installation space.
  • CPCB Compliance: Fully compliant with the latest environmental and emission standards.

Kirloskar Gensets combines cutting-edge technology, efficient design, and reliable performance, ensuring you get the best in class power solutions.

Diesel Generator Set

Enquire Now

For further technical queries,
Mail to info@goelpower.in

Specifications - Kirloskar 250kVA Diesel Generators

Prime Rating at rated RPM (as per ISO 8528)1

Prime rating at rated rpm Kva/ Kw
Genset Model
KG1-250WS
Frequency :
50 Hz
Power Factor :
0.8 lagging
Voltage
415 3Ø V
Governing class
G3
Noise Level
< 75 dBA
Fuel Consumptions
56.9/42.6/29.9
Fuel tank capacity
460 Ltrs
Weight
4100/4500
Overall dimensions of genset
4300/1700/1970
Electrical Battery starting voltage
24 Volts-DC

Engine - Kirloskar 250kVA Diesel Generators

Engine
Engine Model
6SL 1500TA G3
Rated output (KW/ Hp)
228/310
No of Cyliender
6
Cubic Capacity
8.86 Ltrs
Bore x Stroke
118 x 135 mm
Rated Speed
1500 Rpm
Aspiration
TA NA/TC/TA
Lube Oil change period
500 hrs
Lube oil Sump Capacity
27 Ltrs
Coolant Capacity
32 Ltrs
Alternater - Kirloskar 250kVA Diesel Generaters
Insulation Class
Alternator Efficiency (at 100% load) 0.8 pf
Class H
Ingression Protection
IP 23
Alternator Efficiency (at 100% load) 0.8 pf**
93.6
Alternator Efficiency (at 75% load) 0.8 pf**
93.9
Permissible Voltage Dip at Full Load 0.8 pf Lag
≤ 20 %
Time Permitted to build up rated Voltage at Rated RPM
< 5 sec provided engine reach the rated speed sec provided engine reach the rated speed
Short Circuit Ratio
0.629
Short Circuit Withstand Time
3 Times rated current for “3 sec”
Overload Withstand Capacity
10% overload for one hour once in 12 hours